Flow Module

Flow Module Mod X4T Four Channels Flow and Temperature

Mod X420Flow ModuleCommunication ProtocolModel: Mod X420Working Voltage: DC24VIntroductionThis series of products follows the MODBUS protocol instructions. Available command codes are 0x03, 0x06, and

Mod X4T Flow Module

Communication Protocol

Model: Mod X4T

Working Voltage: DC5-24V

Introduction

This series of products follows the MODBUS protocol instructions. Available command codes are 0x03, 0x06, and 0x10. CRC check: low bit first, high bit last.

Example: Use the 03 instruction to read multiple registers

0x010 x030 x000 x000 x000 x030 x050 xCB

(Continuously read the values of 3 registers from the 0x0000 register of device No. 0x0001)

To write to a single register use the 06 instruction

0x01 0x06 0x00 0x01 0x00 0x03 0x19 0xCA

(Write 0x0003 to the 0x0001  register of device No.  0x0001)

Writing to multiple registers uses 10 instructions

0x010 x100 x000 x000 x000 x020 x040 x000 x000 x000 x010 x320 x6F

(Write 0x0000 to the 0x0000 register of device No. 0x0001, and write 0x0001 to the 0x0001 register of device No. 0x0001)

Default Settings:

Baud rate: 9600 (decimal)

MODBUS device address: 1 (decimal)

Flowmeter constant K value: 500 (decimal)

To modify baud rate parameters

The default baud rate is 9600, and the reading is 2.

If you modify the baud rate, modify the parameters as follows. (If you enter a value other than the value in the table, the baud rate will be restored to 9600, but when reading, it will be displayed as the modified value is not 2)

Setting

Baud Rate

0

2400

1

4800

2

9600

3

19200

4115200

Register AddressRegister Function
0x0000Baud Rate
0x0001Device Address, can be modified to 0x0001-0x00F7 (decimal 1-247)
 0x0002Decimal(Default 2: 2 decimals of flow rate) 
0x0003Flow sensor (1) pulse K value, the value read and written is 100 times the actual value (maximum 65535)
0x0004Flow sensor (1) Permanent cumulative flow high register, unit, L (maximum 65535)
0x0005Flow sensor (1) Permanent cumulative flow low register, unit, L (maximum 65535)
0x0006Flow sensor (1) Permanent cumulative flow decimal, the reading is 100 times the actual value, unit, L
0x0007Flow sensor (1) Permanent accumulated flow pulse value(related with 0x0006)(accumulate 1L and return to 0)
0x0008Default:10K Resistance of temperature sensor (1)  (need to write 50K if the sensor is NTC50K)
0x0009Flow sensor (2) pulse K value, the value read and written is 100 times the actual value (maximum 65535)
0x000AFlow sensor (2) Permanent cumulative flow high register, unit, L (maximum 65535)
0x000BFlow sensor (2) Permanent cumulative flow low register, unit, L (maximum 65535)
0x000CFlow sensor (2) Permanent cumulative flow decimal, the reading is 100 times the actual value, unit, L
0x000DFlow sensor (2) Permanent accumulated flow pulse value(related with 0x0006)(accumulate 1L and return to 0)
0x000EDefault:10K Resistance of temperature sensor (2)  (need to write 50K if the sensor is NTC50K)
0x000FFlow sensor (3) pulse K value, the value read and written is 100 times the actual value (maximum 65535)
0x0010Flow sensor (3) Permanent cumulative flow high register, unit, L (maximum 65535)
0x0011Flow sensor (3) Permanent cumulative flow low register, unit, L (maximum 65535)
0x0012Flow sensor (3) Permanent cumulative flow decimal, the reading is 100 times the actual value, unit, L
0x0013Flow sensor (3) Permanent accumulated flow pulse value(related with 0x0006)(accumulate 1L and return to 0)
0x0014Default:10K Resistance of temperature sensor (3)  (need to write 50K if the sensor is NTC50K)
0x0015Flow sensor (4) pulse K value, the value read and written is 100 times the actual value (maximum 65535)
0x0016Flow sensor (4) Permanent cumulative flow high register, unit, L (maximum 65535)
0x0017Flow sensor (4) Permanent cumulative flow low register, unit, L (maximum 65535)
0x0018Flow sensor (4) Permanent cumulative flow decimal, the reading is 100 times the actual value, unit, L
0x0019Flow sensor (4) Permanent accumulated flow pulse value(related with 0x0006)(accumulate 1L and return to 0)
0x001ADefault:10K Resistance of temperature sensor (4)  (need to write 50K if the sensor is NTC50K)
0x001BFlow sensor (1) Temporary accumulated flow high register, unit, L (maximum 65535)
0x001CFlow sensor (1) Temporary accumulated flow low register, unit, L (maximum 65535)
0x001DFlow sensor (1) Temporary cumulative flow decimal, the reading is 100 times the actual value, unit, L
0x001EFlow sensor (1) Temporary accumulated flow pulse value(related with 0x000C) (accumulate 1L and return to 0)
0x001FFlow sensor (1) Real-time flow rate, unit: L/min, the reading is 100 times the actual value
0x0020Flow sensor (1) Real-time pulse number unit Hz, the reading is 100 times the actual value
0x0021Temperature  (1) reading Unit: ℃  the reading is 100 times the actual value
0x0022Flow sensor (2) Temporary accumulated flow high register, unit, L (maximum 65535)
0x0023Flow sensor (2) Temporary accumulated flow low register, unit, L (maximum 65535)
0x0024Flow sensor (2) Temporary cumulative flow decimal, the reading is 100 times the actual value, unit, L
0x0025Flow sensor (2) Temporary accumulated flow pulse value(related with 0x000C) (accumulate 1L and return to 0)
0x0026Flow sensor (2) Real-time flow rate, unit: L/min, the reading is 100 times the actual value
0x0027Flow sensor (2) Real-time pulse number unit Hz, the reading is 100 times the actual value
0x0028Temperature  (2) reading Unit: ℃  the reading is 100 times the actual value
0x0029Flow sensor (3) Temporary accumulated flow high register, unit, L (maximum 65535)
0x002AFlow sensor (3) Temporary accumulated flow low register, unit, L (maximum 65535)
0x002BFlow sensor (3) Temporary cumulative flow decimal, the reading is 100 times the actual value, unit, L
0x002CFlow sensor (3) Temporary accumulated flow pulse value(related with 0x000C) (accumulate 1L and return to 0)
0x002DFlow sensor (3) Real-time flow rate, unit: L/min, the reading is 100 times the actual value
0x002EFlow sensor (3) Real-time pulse number unit Hz, the reading is 100 times the actual value
0x002FTemperature  (3) reading Unit: ℃  the reading is 100 times the actual value
0x0030Flow sensor (4) Temporary accumulated flow high register, unit, L (maximum 65535)
0x0031Flow sensor (4) Temporary accumulated flow low register, unit, L (maximum 65535)
0x0032Flow sensor (4) Temporary cumulative flow decimal, the reading is 100 times the actual value, unit, L
0x0033Flow sensor (4) Temporary accumulated flow pulse value(related with 0x000C) (accumulate 1L and return to 0)
0x0034Flow sensor (4) Real-time flow rate, unit: L/min, the reading is 100 times the actual value
0x0035Flow sensor (4) Real-time pulse number unit Hz, the reading is 100 times the actual value
0x0036Temperature  (4) reading Unit: ℃  the reading is 100 times the actual value

 

Note:

1. After the address, baud rate, K factor, and permanent cumulative flow are modified, the device needs to be restarted to take effect.

2. Please close the input pipeline before clearing the cumulative flow to prevent water from passing by again after clearing. The value changes after 60 seconds, and the program changes the value again so that the cumulative amount cannot be returned to zero.

3. Reset the temporary cumulative flow after power failure, and record the permanent cumulative flow every 60 seconds. (Flows must exceed 1 litre within 60 seconds to be recorded)

4. When the low bit of the register is full of 65535, it will enter 1 into the higher bit. Example: Assuming a flow sensor with a cumulative flow higher register is 1 and the cumulative flow lower register is 2; then the total flow is 65535 * 1 +2 = 65537L

5. The maximum storage value of each register is 65,535, and the maximum storage data of the permanent cumulative flow of each flow sensor is 65,535 * 65,535 +65,535 = 4,294,917,600 liters of water

6. During the reset operation, the registers for the permanent accumulated traffic need to be reset at the same time, that is, the registers 3/4/5/6 should be reset at the same time. Temporary cumulative traffic reset is also subject to this rule.

Wiring instructions: